AvailableTransformer package

2 × 2,600 kVA Eaton transformers — damaged repair package

High-voltage winding34,500 V deltaDelta
Low-voltage winding416Y/240 VWye with neutral

Winding ratings are shown independently of application direction. Confirm duty, grounding, protection and compatibility before use.

2,600 kVA each · 5,200 kVA package total (2 units) · Eaton · Lufkin, Texas, U.S.

Same transformers, two options

The equipment is currently damaged. The repair option describes proposed work on these same assets; it is not additional ready-to-use inventory.

PARTS / AS-IS

Existing damaged condition

2,600 kVA each · 5,200 kVA package total (2 units) nameplate. See the photographs and condition report for the recorded damage.

Acquire in the existing condition for parts or a buyer-managed repair. The nameplate is not a statement of current serviceability.

REPAIR OPTION · PROPOSED

Repair and return-to-service scope

Request a repair proposal targeting the existing nameplate and winding configuration. No change to voltage, frequency or kVA is assumed.

  1. Inspect and document damage; establish whether an economic repair is feasible.
  2. Agree repairs and replacement components from the inspection findings.
  3. Agree electrical, insulation and fluid tests, acceptance criteria and a documented release for service with the repair provider.

Schedule, price and warranty: to be quoted after inspection and scope agreement. No repair has been completed or warranted under this proposed option.

Package and individual selections refer to the same two serial-numbered assets. A repair request reserves no additional units and does not certify the damaged equipment for energization.

Technical review & next steps

Before energization: confirm the selected serial number, actual nameplate, fluid condition, inspection and testing scope. Repair-group units require repair and testing.

Guides open in a new tab.

History, availability and verification

Estimated dispatch
Ask about timing
Dispatch conditions
Confirm release, loading and freight. Dispatch timing does not mean tested or ready to energize.
Condition notes
Repair group: one pinhole radiator leak and one X0 lug/nut leak; low fluid reported on both. The latest source does not map defect type to individual serials. Confirm selected-unit repair scope and test before energization.
Photograph basis
New gallery images are representative of the offered lot or sample documents, not confirmed as the selected serial.
Quantity basis
2 physical transformers; shared with individual serial listings.
Availability last checked
2026-09-22

Assets included in this package

This is a grouping of the assets below. Individual and package listings overlap; quantities and power must not be added together.

Package availability depends on every included asset. Confirm the final schedule before purchase.

Voltage configurations

Documented primary winding settings (V)
32780;33640;34500;35360;36220
Search cross-reference
415 V searches also show this listing. Actual nameplate voltage is shown above; verify compatibility independently.

Photographs & identification

Representative lot photographs (4)
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative technical documents (2)
Representative Eaton nameplate; confirm selected serial — source deck page 3. Not mapped to an individual serial.
Representative Eaton nameplate; confirm selected serial — source deck page 3. Not mapped to an individual serial.
Representative Eaton general arrangement drawing — source deck page 7. Not mapped to an individual serial.
Representative Eaton general arrangement drawing — source deck page 7. Not mapped to an individual serial.
Equipment photographs (1)
Previous cover photo — retained for reference
Previous cover photo — retained for reference

Equipment overview

Two 2,600 kVA units (5.2 MVA total) from the Eaton copper-wound FR3 padmounted transformer offering. Representative configuration: 34,500 V delta primary to 416Y/240 V secondary, three-phase, 60 Hz.

Repair group: one pinhole radiator leak and one X0 lug/nut leak; low fluid reported on both. The latest source does not map defect type to individual serials. Confirm selected-unit repair scope and test before energization.

The photographed sample plate shows five discrete primary tap settings: 36,220; 35,360; 34,500; 33,640; 32,780 V. Confirm the selected serial and actual plate before applying these representative values. These settings do not establish a continuous operating-voltage range.

Copper primary and secondary windings; FR3 natural ester fluid; representative KNAN cooling, 65°C rise and 5.81% impedance. Inspect actual accessories, fluid, grounding, protection and terminals. Nameplate totals do not establish grid availability or usable site power.

Approximate per-unit envelope 104.4 × 80.7 × 84.8 in; representative total weight 15,408 lb. Verify lifting points, transport dimensions, pad and clearances. Individual listings and package memberships refer to the same physical equipment. Request selected-unit records, inspection, test scope and a quotation.

Additional listing details

Listing Reference
EE-EATON-P2D

Transformer specifications

Primary winding
34,500 V delta
Secondary winding
416Y/240 V
Primary Connection
Delta
Secondary Connection
Wye with neutral
Vector Group
DY1 (representative plate; verify selected unit)
Tap Changer
Off Circuit
Tap Range
32,780–36,220 V
Tap Positions
5
Winding Material
Copper
Temperature Rise
65 °C
Enclosure / Mounting
Outdoor padmounted, loop feed
View individual tap values
Representative sample plate: 36220; 35360; 34500; 33640; 32780 V. Verify each selected unit; de-energized adjustment per OEM instructions.

Additional specifications

Representative sample impedance
5.81%; verify actual selected-unit nameplate and test report
Fluid volume
689 gallons per unit, representative documentation; actual fluid level to verify
Representative primary bushings
Six 600 A, 35 kV deadbreak bushings; verify installed equipment
Representative secondary terminals
Four 6-hole spade bushings; X0 with ground strap
Representative protection
38 kV Bay-O-Net plus current-limiting fusing; verify ratings
Representative switch
Four-position open-transition; verify duty and configuration
Representative monitoring
Temperature, liquid-level and pressure-vacuum gauges; alarm contacts
Representative sample date
October 2022; verify each selected serial
Calculated rated LV current
Approximately 3,609 A at 416 V, three-phase, 2,600 kVA; not a terminal rating
OEM warranty
No remaining OEM warranty represented

Current inventory