2,600 kVA Eaton FR3 copper transformer — 22JC208360079

High-voltage winding34,500 V deltaDelta
Low-voltage winding416Y/240 VWye with neutral

Winding ratings are shown independently of application direction. Confirm duty, grounding, protection and compatibility before use.

2,600 kVA per unit · Eaton · Lufkin, Texas, U.S.

Technical review & next steps

Before energization: confirm the selected serial number, actual nameplate, fluid condition, inspection and testing scope. Repair-group units require repair and testing.

Guides open in a new tab.

History, availability and verification

Serial / identifier
22JC208360079
Estimated dispatch
Immediate
Dispatch conditions
Confirm release, loading and freight. Dispatch timing does not mean tested or ready to energize.
Condition notes
Unused surplus, excellent condition per seller. Storage condition and electrical acceptance testing require selected-unit verification. No remaining OEM warranty represented.
Photograph basis
New gallery images are representative of the offered lot or sample documents, not confirmed as the selected serial.
Quantity basis
One of 13 undamaged units.
Availability last checked
2026-09-22

Also included in: 13 × 2,600 kVA Eaton FR3 copper transformers — unused package. The same asset is counted once.

Voltage configurations

Documented primary winding settings (V)
32780;33640;34500;35360;36220
Search cross-reference
415 V searches also show this listing. Actual nameplate voltage is shown above; verify compatibility independently.

Photographs & identification

Representative lot photographs (4)
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative Eaton lot photograph — source deck page 5. Not mapped to an individual serial.
Representative technical documents (2)
Representative Eaton nameplate; confirm selected serial — source deck page 3. Not mapped to an individual serial.
Representative Eaton nameplate; confirm selected serial — source deck page 3. Not mapped to an individual serial.
Representative Eaton general arrangement drawing — source deck page 7. Not mapped to an individual serial.
Representative Eaton general arrangement drawing — source deck page 7. Not mapped to an individual serial.

Equipment overview

One 2,600 kVA unit from the Eaton copper-wound FR3 padmounted transformer offering. Representative configuration: 34,500 V delta primary to 416Y/240 V secondary, three-phase, 60 Hz.

Unused surplus, excellent condition per seller. Storage condition and electrical acceptance testing require selected-unit verification. No remaining OEM warranty represented.

The photographed sample plate shows five discrete primary tap settings: 36,220; 35,360; 34,500; 33,640; 32,780 V. Confirm the selected serial and actual plate before applying these representative values. These settings do not establish a continuous operating-voltage range.

Copper primary and secondary windings; FR3 natural ester fluid; representative KNAN cooling, 65°C rise and 5.81% impedance. Inspect actual accessories, fluid, grounding, protection and terminals. Nameplate totals do not establish grid availability or usable site power.

Approximate per-unit envelope 104.4 × 80.7 × 84.8 in; representative total weight 15,408 lb. Verify lifting points, transport dimensions, pad and clearances. Individual listings and package memberships refer to the same physical equipment. Request selected-unit records, inspection, test scope and a quotation.

Additional listing details

Listing Reference
EE-EATON-079

Transformer specifications

Transformer Capacity
2,600 kVA
Primary winding
34,500 V delta
Secondary winding
416Y/240 V
Primary Connection
Delta
Secondary Connection
Wye with neutral
Vector Group
DY1 (representative plate; verify selected unit)
Tap Changer
Off Circuit
Tap Range
32,780–36,220 V
Tap Positions
5
Cooling Class
KNAN
Winding Material
Copper
Insulating Fluid
FR3
Temperature Rise
65 °C
Enclosure / Mounting
Outdoor padmounted, loop feed
View individual tap values
Representative sample plate: 36220; 35360; 34500; 33640; 32780 V. Verify each selected unit; de-energized adjustment per OEM instructions.

Additional specifications

Representative sample impedance
5.81%; verify actual selected-unit nameplate and test report
Fluid volume
689 gallons per unit, representative documentation; actual fluid level to verify
Representative primary bushings
Six 600 A, 35 kV deadbreak bushings; verify installed equipment
Representative secondary terminals
Four 6-hole spade bushings; X0 with ground strap
Representative protection
38 kV Bay-O-Net plus current-limiting fusing; verify ratings
Representative switch
Four-position open-transition; verify duty and configuration
Representative monitoring
Temperature, liquid-level and pressure-vacuum gauges; alarm contacts
Representative sample date
October 2022; verify each selected serial
Calculated rated LV current
Approximately 3,609 A at 416 V, three-phase, 2,600 kVA; not a terminal rating
OEM warranty
No remaining OEM warranty represented

Current inventory

Related equipment